FLEXURAL STRENGTH PERFORMANCE OF FIBERGLASS REINFORCED CONCRETE

Student: Paul Akpan Bassey
Supervisor: Dr Chioma Awodiji
HOD: Dr Sule Samuel
Department of Civil Engineering
Engineering
University of Port-Harcourt, Rivers State

Abstract

This study examined the flexural strength performance of fiberglass-reinforced concrete (FRC), focusing on the effects of fiberglass content and curing duration. Using a mix design of 1:2:3, a water-cement ratio of 0.55, and 12 mm fiberglass strands, beam specimens (150 mm × 150 mm × 450 mm) were cast and cured for 7, 14, and 28 days. Flexural strength tests conducted via third-point loading showed significant improvements with fiberglass addition. The 4% mix outperformed the control (0% fiberglass) by 15%, 22%, and 30% at 7, 14, and 28 days, respectively, achieving maximum strength of 6.98 MPa at 28 days. However, the 6% mix exhibited a performance decline, likely due to reduced workability and uneven fiber distribution. These findings demonstrate the potential of fiberglass reinforcement in optimizing concrete’s structural performance and highlight the importance of maintaining an optimal fiberglass content for balanced workability and strength enhancement.

Full-Text Access Notice

In accordance with the NERD Policy on promoting peer-reviewed publication, public access to the full text of a project, thesis or dissertation is restricted for three years, allowing the author and supervisors sufficient time to pursue peer-reviewed publication. During this period, researchers with legitimate academic or research purposes may request authorisation directly from the author to enable NERD to release the indexed full texts of the work using the form below.