A TECHNO-ECONOMIC ANALYSIS OF A LOW VOLTAGE ALTERNATING CURRENT SMART GRID
Abstract
The report on a techno-economic analysis of a low voltage alternating current (LVAC) smart grid
is for the purposes of providing reliable, efficient, and intelligent distribution of electricity to
consumers in the Akwa Ibom State University (AKSU) main campus. The presented work assumes
that recent advancements in power electronics, communication technologies and data analytics
have been taken advantage of in order to enable real time monitoring, control and optimization of
the LVAC grid performance. The analysis presented is for a grid designed to handle distributed
energy resources (DERs) such as photovoltaic solar and battery-based energy storage systems. The
extent of the present conventional LVAC grid serving AKSU main campus was determined with
the aid of Google map and by physical inspection of the major blocks and by tracing of the low
voltage lines serving the campus. Measurement of the total power consumption for the campus
was obtained by taking hourly readings from the digital display of the 500kVA backup diesel
generator serving the campus over a 4-day period. Mapping of the main campus and a top-level
design of a smart fault protection scheme was carried out using the AutoCAD software. The
campus was modelled into a seventeen bus system to represent all the departments in the main
campus and possible power generation from solar-based DERs was simulated using Power World
simulator software version 15.0. However, due to the high complexity of a seventeen bus system,
the system was reduced to a four bus system, using four departments (Faculty of Education,
Agricultural Engineering Department, Chemical Engineering Department and Electrical and
Electronic Engineering Department) as a case study. A comparative cost analysis was performed
using the cubic cost model (for diesel-based power generation) and a multi-year tariff order-based
model (for PV and utility sourced power). The graphs of cost (N/kWh) against time in hours (hrs),
were used to illustrate the total hourly cost incurred when the campus is served from public utility
supply and graph of PV generation potential (kWh) against time (hrs) gives the total power
generated when solar based DERs was used to serve the campus, results showed that integration
of solar based DERs with other conventional sources of power supply in AKSU main campus is a
viable choice. Therefore, it is recommended that the campus be served with solar based DERs and
the excess PV generated energy used to feed other departments or stored in battery-based energy
storage systems for future use.
Full-Text Access Notice
In accordance with the NERD Policy on promoting peer-reviewed publication, public access to the full text of a project, thesis or dissertation is restricted for three years, allowing the author and supervisors sufficient time to pursue peer-reviewed publication.
During this period, researchers with legitimate academic or research purposes may request authorisation directly from the author to enable NERD to release the indexed full texts of the work using the form below.